Understand the two interfaces
The adapter has a relationship to the existing curb below and to the replacement equipment above. Those two layouts may differ in size and in the position of their supply and return openings.
Begin with the make and model of both units, the replacement equipment drawings and measurements of the existing curb. Model information helps identify the equipment; field measurements describe what is actually on the roof. Keep both in the project package.
Map the openings separately from the perimeter
Draw the existing curb in plan view and label supply and return. Dimension the openings and their positions from named outside edges. Then identify the corresponding openings on the new equipment drawing.
Two units can have similar outside dimensions but different opening arrangements. Conversely, a larger unit may need an adapter that extends beyond the old curb. The relationship between the openings and the perimeter is what needs to be resolved.

Choose an orientation that everyone can follow
Mark a fixed reference on the roof plan: the access-panel side, a nearby wall or a building direction. Keep that reference on both the existing and proposed layouts. It prevents an otherwise complete set of measurements from being interpreted as a mirrored arrangement.
Look beyond the curb edge
The new equipment and adapter need to be considered alongside nearby walls, vents, other units and service access. Include those obstacles on the roof layout, especially where the replacement unit changes size or position.
Record the roof pitch and proposed height where they affect the installation. Support, attachment and project requirements also belong in the review; an adapter is not simply a sheet metal cover placed over an opening.

Use photos to explain uncertain conditions
A wide photo shows the surrounding roof. Closer views show curb corners, opening edges and existing connections. Together they explain more than several nearly identical photos of the equipment cabinet.
If roofing, flashing or the existing unit hides a critical dimension, identify the uncertainty. The installing team can determine how to verify it. Copying an approximate dimension into a final drawing makes the uncertainty harder to see.
Before the adapter is released
Every changeout is specific to its equipment and roof conditions. Send the drawings and field information together so the adapter can be discussed as part of the complete installation.
- Compare the existing curb measurements with the proposed bottom connection.
- Check the replacement model, opening sizes and supply/return orientation.
- Review height, overhang, adjacent obstructions and service access.
- Resolve any unverified field dimensions and project support or attachment requirements.