Start with a labeled route
Draw the main run, then label every branch and change of direction. Give each piece a number that can be used on the drawing and in a quantity list. The sketch does not need to be artistic; it needs to show which opening connects to which.
Put an airflow arrow on the layout and identify any connection to equipment or existing duct. If a section is fixed by field conditions, distinguish its verified dimensions from the lengths you are proposing.
An elbow needs more than a diameter
An elbow has a turn angle and a bend radius as well as a connection diameter. Those details affect how much room the turn occupies. “A 12-inch elbow” leaves the turn geometry unresolved.
The round-duct form gives you a place to record the required fitting. Include the angle, radius if specified and the available space around the bend. Where a project has a specified fitting geometry, send that requirement rather than substituting a different shape based on diameter alone.

Locate branches from one reference end
For a tap or branch, record its diameter and where it connects to the main run. State whether the location is measured to the branch centerline or to an edge. Also show which way the branch faces.
Measuring several branch positions from the same named end makes the layout easier to interpret than chaining approximate distances from one branch to the next.
Describe the mating ends
A fitting must join the part beside it. Include the specified coupling, flange or other end detail, especially when matching existing work. A close photograph of the existing connection can help explain what needs to mate.
Define what your length includes. Overall piece length and installed distance between connection faces are not always the same measurement. Keep the same convention on the sketch and the order list.
Treat transitions as two openings and a length
A round-to-round reducer needs the diameter at each end and the length between them. A rectangular-to-round transition also needs the rectangular width and height, plus the position of the round collar.
State whether the openings share a centerline or whether one is offset. If the transition must sit flat against a surface, identify the face that needs to remain aligned.

Keep the request together
If you are replacing part of an existing run, include a wide photo of the route and close views of both ends. The layout explains the system; the close views explain the connections.
- A numbered layout and quantity for every piece.
- Diameters, straight lengths and the geometry of each turn.
- Branch positions, directions and the reference used for measurement.
- End connections and any specified material, thickness or liner.